Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Nominal Voltage: | 936V |
| Warranty: | 1 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| DC Battery Parameters | |
| Battery Cell Type | LFP 3.2V/280Ah |
| Battery Pack Configuration | 46.59kWh/1P52S |
| Battery System Configuration | 232kWh/1P260S |
| Battery Voltage Range | 728~936V DC |
| AC Side Parameters | |
| AC Rated Power | 116kW |
| AC Maximum Power | 128kW (continuous for 1min) |
| AC Current Distortion Rate | <3% |
| DC Component | <0.5%Ipn |
| Grid Rated Voltage | 400V AC |
| Adjustable Power Factor Range | -1~1 |
| Rated Grid Frequency | 50Hz |
| System Parameters | |
| Energy Conversion Efficiency | ≥91% |
| Charge/Discharge Rate | ≤0.5P |
| Discharge Depth | 95%DOD |
| Number of Cycles | ≥8,000 times |
| Charge/Discharge Switching Time | <100ms |
| Communication Interface | Ethernet /RS485 |
| Protection Level | IP55 |
| Cooling Method | Liquid Cooling |
| Operating Temperature | -25~55ºC |
| Relative Humidity | 0-95%RH, non-condensing |
| Noise | <75dB |
| Altitude | ≤2,000m (derating for usage above 2,000m) |
| Fire Suppression System | Combustible gas detection/smoke detection/temperature detection + active warning + module-level fire suppression (perfluorohexanone) |
| Dimensions (Width*Depth*Height) | 1,100*1,300*2,350 (mm) |
| Weight | 2,800kg |